What about the RFID room asset management? Equipment and cable markings.
Industry News

What about the RFID room asset management? Equipment and cable markings.

PublishedShanghai Zejie Smart Technology Co., Ltd.

What are the cores to be solved by RFID for machine room asset management?

The assets in the room are divided into two main blocks: one is visible equipment - servers, switches, routers, UPS, air-conditioning modules; the other is hidden behind the cabinet, on line frames, and network and power cables on bridge shelves. RFID (radio recognition, simply a readerZZ) is the value of each asset in the room, which allows both types to be batched without demanturing, with constant electricity.

The equipment is marked differently from the cable. The device has a flat shell that can be labelled, and the pair model can be read in a stable manner; the cables are flexible, have different diameters, walk with metal bridges, and require both the carving of labels and resistance to metals. Below is a few questions that readers ask most frequently.

What frequency does the RFID labels use?

Server rooms generally use UHF (860–960 MHz), which has a read range of 1–10 m. Fixed or handheld readers can count assets in batches. HF (13.56 MHz, usually with a range of no more than 10 cm) performs well around metal, but bulk counts are too slow, so it is rarely used in server rooms.

One thing to be aware of when choosing a frequency segment: If the UHF label is placed directly on the metal cabinet or server surface, reading distance will shrink significantly and even completely. So the machine room will have to use a specially designed "anti-metal label" with different internal structures and general labels, an isolated metal suction material or special antenna design. We'll have to step through this pit in the project -- the first figure saves from using a normal non-dry-deductible tag to paste the shell of the server, and then several devices in the same cabinet interfere with each other, and the readers sweep out a bunch of pieces of broken codes, and then all of them are replaced by anti-metallic tags.

What exactly does the equipment mark do?

Servers, switches, storage devices, which are "visible assets", usually labeled before the factory or on the shelf.

The following are the three types of information that you can write on each label:

The location of the label is also regulated. It is usually placed on the inside side of the cabinet, on the top or on the side of the device in a non-dispersible area, and avoids being placed near the power interface and above the metal sign. The labels for multiple devices in the same cabinet are preferably directed to the outside, so that the reader antenna can be read at once through the machine's corridor.

Why is cable marking harder than equipment?

There are three problems with cable marking:

First, the cable is cylindrical and bends, and a normal hard label can't be pasted. It needs flexible metal-resistant labels -- it bends to a certain angle, and sometimes it's a tight "wire-coated cord tag" that can be rounded.

Second, cables are usually bound to a bridge, and multiple multiple-timed tags cover each other. We find in our project that if 24 jump lines are posted on both ends of the line, the reader identifies at most 70% when it's done, with several missing points in the middle. Then they are labeled independently for every jumper, and the count is stable to over 98%.

Third, the cable connects to different ports at both ends of the line, and the label identifies "where to go." So writing an asset ID is not enough, usually with a linked tag pair on each end of the cable or with information about the port location of the starting and termination end in the tag.

Two common forms of cable labels

Type Applications Read-outs reference
Soft non-dry glue labels Smaller diameter jump, fiber-optic jump. 1-3 meters
Wire-coated RFID tag Power cables, thicker copper cables, power-driven routes. 2-5 meters.

How does a reader fit?

The readers in the machine room are in two categories:Fixed Reader(Scanning area with antennas at both ends of the cabinet tunnel or at the entrance to the machine room) andHandheld Reader(The inventory personnel are holding their hands close to the asset scan).

Fixed-based readers are suitable for "Autocal Counts of Accessing and Into the Machine Room" -- such as a pair of antennas and readers at the door of the machine room, automatic recording of time, direction and asset ID when all tagged equipment or cables pass through. After using this option in the room of a medium Internet company, an entry/exit asset does not need to be manually registered on a daily basis, and the system automatically generates desktop accounts.

Handheld readers are suitable for "regular count" and "location to find an asset." For example, when you get a list saying "a server malfunction", the administrator goes through the locker with the handler, reads the corresponding labels and the device beeps or vibrates, and can be located in seconds, much faster than flipping the paper table.

An antenna is located in a specific location: the UHF antenna is directed, usually installed at 45 degrees below the top of the cabinet channel, covering the equipment labels of the cabinets on both sides. The cable tags are hidden in the line frame, with higher reading distance requirements, and may require an array of antennas on each side of the line.

What are the most easily stepped-in pits in the implementation process?

Based on our experience with the RFID project in the hangar, the common problems are concentrated in four areas:

1. The label type is wrong.There are different label models for different metal surfaces, different cable diameters, and no food-for-food formula. It is more prudent to buy several models in small quantities, 10-20 for real, reading distance and sticky strength, and then batch type.

2. Reader power is too high.UHF readers with a power above certain thresholds trigger local radio management regulations, and may interfere with other wireless devices in the machine room. The normal fixed-readers are between 1 and 4W, and handheld is between 0.5 and 2W, just with appropriate antenna gain.

3. Software interfaces were not accessible.The RFID tag is only a "hard ID" and the real asset management is still in the asset management system. The inventory data is automatically entered into the system's database, and the map of the label and the asset number is created once and for all at the time the system is initialized. Any missing link in the middle is left to the Excel table.

4. Label maintenance is not in place.The room's temperature fluctuates, the humidity is wet, and dust affects the label life. It is recommended that a sample of the inventory be done every year, checking off, damaging, unreadable tags, and changing them in time. We have seen a room run for three years, about 5% of the cabinet outside is subsidized by repeated heat.

What is a complete RFID asset management process?

In a series of points, the standard implementation process is approximately five steps:

  1. Asset inventory and code• A full inventory of existing equipment, ports and cables in the room, with a single asset number assigned to each, and a labeled EPC coding programme;
  2. Tab Selection & Sample• Purchase of 2-3 label samples, based on the type of equipment, cable specifications and adhesion, to measure reading distance and strength in the physical environment;
  3. Batch Paste and Tie• Print or write tags by coding programme, physically attach them to the asset and create a map of labeled ID and asset information in the asset management system;
  4. Reader and antenna deploymentInstallation of fixed-style readers, antennas, configuration of handheld machines, setting of scanning areas and trigger logic;
  5. System Interconnection and Test Run: Access the read and writer data to the asset management system, do simulation counts and abnormal scene tests, and then formally go online after the problem is closed.

After the whole process is completed, it usually takes 2-4 weeks for a medium-sized room of 200 to 500 containers (detailing the number of assets). Shanghai-based RFID asset projects in multiple rooms by Shanghai-based Skill Ltd., which can keep the drop rate on the initial round count below 2%.

I'll put "tweak it, read it" first and talk about the other.

The RFID asset management is not done with a few reading and writing machines, but at the core is to put "up" on it, read it correctly, find "tightly." The device identification is relatively simple, and choosing metal tags and standard adhesion positions can solve; cable markings are more complex, and require a balance of bending, relevance and mass-reading efficiency. More small-volume measurements before implementation, the implementation of an interface with the asset management system, and regular maintenance of the label after implementation, will make this system work. If you don't know what kind of label you should choose for your own room, you can start by putting out a list of the type of equipment and the cable specifications, and get an experienced vendor to do a sample-on-site test, which will work on more than a multi-parameter.